The loss of power from the UPS units caused a loss of all the following: the control room annunciators, the safety parameter display system computer, control rod position indication, the plant process computer, the core thermal limits computer, the feedwater control system, some of the lighting for the plant, the plant radio and paging systems, some instrumentation for balance-of-plant systems, and some instrument recorders. The loss of control room annunciators concurrent with the plant transient resulting from automatic tripping of the main generator, main turbine, and reactor caused the licensee (Niagara Mohawk) to declare a site area emergency in accordance with the site emergency plan.
Spanish[es]
La pérdida de energía a partir de las unidades de UPS provocaron una pérdida de los pilotos de aviso de la sala de control, el sistema de pantallas de ordenador que muestran los parámetros de seguridad, la indicación de la posición de las barras de control, el ordenador de proceso de la planta, el ordenador de los límites de calor del núcleo, el sistema de control de suministro de agua, parte de la iluminación de la planta, la radio de la planta, parte de la instrumentación de motivaron que el licenciatario de la instalación (Niagara Mohawk Corporation) declarara la emergencia del área de emplazamiento de acuerdo con su plan de emergencia.